<zabbix_export><version>5.0</version><date>2021-11-21T22:07:57Z</date><groups><group><name>Retificadores</name></group></groups><templates><template><template>Vertiv</template><name>Vertiv</name><description>## Overview

https://github.com/Mihguel-Araujo/Template-Zabbix/blob/main/Template%20Vertiv



## Author

Mihguel da Silva Santos Tavares de Araujo

</description><groups><group><name>Retificadores</name></group></groups><applications><application><name>Inform</name></application><application><name>Operational</name></application></applications><items><item><name>Battery 2 Capacity</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.5.8.0</snmp_oid><key>fBattery2Capacity</key><units>%</units><applications><application><name>Operational</name></application></applications><triggers><trigger><expression>{last(#2)}&lt;99</expression><name>Battery 2 Capacity on {HOST.NAME}</name><priority>HIGH</priority></trigger></triggers></item><item><name>Battery 1 Capacity</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.5.3.0</snmp_oid><key>ifBattery1Capacity</key><units>%</units><applications><application><name>Operational</name></application></applications><triggers><trigger><expression>{last(#1)}&lt;90</expression><name>Battery 1 Capacity on {HOST.NAME}</name><priority>HIGH</priority></trigger><trigger><expression>{last(#1)}&lt;50</expression><name>Battery 1 on Half {HOST.NAME}</name><priority>HIGH</priority></trigger></triggers></item><item><name>Battery 1 Current</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.5.2.0</snmp_oid><key>ifBattery1Current</key><value_type>FLOAT</value_type><units>A</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>Battery 2 Current</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.5.7.0</snmp_oid><key>ifBattery2Current</key><value_type>FLOAT</value_type><units>A</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>Battery Voltage</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.5.1.0</snmp_oid><key>ifBatteryVoltage</key><value_type>FLOAT</value_type><units>V</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>Capacidade da Bateria (%)</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.5.13.0</snmp_oid><key>ifCapacidadeBateria</key><value_type>FLOAT</value_type><units>%</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing><triggers><trigger><expression>{last(#1)}&lt;90</expression><name>Bateria Descarregando {HOST.NAME}</name><status>DISABLED</status><priority>HIGH</priority><manual_close>YES</manual_close></trigger><trigger><expression>{last(#1)}&lt;50</expression><name>Bateria Na Metade {HOST.NAME}</name><status>DISABLED</status><priority>DISASTER</priority><manual_close>YES</manual_close></trigger></triggers></item><item><name>System Current</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.3.0</snmp_oid><key>ifSystemCurrent</key><value_type>FLOAT</value_type><units>A</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>System Status</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.1.0</snmp_oid><key>ifSystemStatus</key><applications><application><name>Operational</name></application></applications></item><item><name>System Used Capacity</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.4.0</snmp_oid><key>ifSystemUsedCapacity</key><value_type>FLOAT</value_type><units>%</units><applications><application><name>Operational</name></application></applications></item><item><name>System Voltage</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.2.0</snmp_oid><key>ifSystemVoltage</key><value_type>FLOAT</value_type><units>V</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>psTemperature1</name><type>SNMP_AGENT</type><snmp_oid>1.3.6.1.4.1.6302.2.1.2.7.1.0</snmp_oid><key>ps1.temperature[upsHighPrecBatteryTemperature]</key><history>7d</history><value_type>FLOAT</value_type><units>℃</units><description>MIB: PowerNet-MIB&#13;
The current internal UPS temperature in Celsius.&#13;
 Temperatures below zero read as 0.</description><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>psTemperature2</name><type>SNMP_AGENT</type><snmp_oid>1.3.6.1.4.1.6302.2.1.2.7.2.0</snmp_oid><key>ps2.temperature[upsHighPrecBatteryTemperature]</key><history>7d</history><value_type>FLOAT</value_type><units>℃</units><description>MIB: PowerNet-MIB&#13;
The current internal UPS temperature in Celsius.&#13;
 Temperatures below zero read as 0.</description><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>psStatusBatteryMode</name><type>SNMP_AGENT</type><snmp_oid>1.3.6.1.4.1.6302.2.1.2.9.0</snmp_oid><key>psbattery.status[upsBasicBatteryStatus]</key><history>7d</history><description>MIB: PowerNet-MIB&#13;
The status of the UPS batteries. A batteryLow(3) value&#13;
 indicates the UPS will be unable to sustain the current&#13;
 load, and its services will be lost if power is not restored.&#13;
 The amount of run time in reserve at the time of low battery&#13;
 can be configured by the upsAdvConfigLowBatteryRunTime.&#13;
 A batteryInFaultCondition(4)value indicates that a battery&#13;
 installed has an internal error condition.</description><applications><application><name>Operational</name></application></applications><valuemap><name>PowerNet-MIB::upsBasicBatteryStatus</name></valuemap><preprocessing><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing><triggers><trigger><expression>{last(0)}=3</expression><name>The battery power is too low to support the load on {HOST.NAME}</name><priority>DISASTER</priority></trigger></triggers></item><item><name>Input Line A Current</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.6.4.0</snmp_oid><key>psInputLineACurrent</key><value_type>FLOAT</value_type><units>A</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>Input Line A Voltage</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.6.1.0</snmp_oid><key>psInputLineAVoltage</key><value_type>FLOAT</value_type><units>V</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>Input Line B Current</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.6.5.0</snmp_oid><key>psInputLineBCurrent</key><value_type>FLOAT</value_type><units>A</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>Input Line B Voltage</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.6.2.0</snmp_oid><key>psInputLineBVoltage</key><value_type>FLOAT</value_type><units>V</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>Input Line C Current</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.6.6.0</snmp_oid><key>psInputLineCCurrent</key><value_type>FLOAT</value_type><units>A</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>Input Line C Voltage</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.6.3.0</snmp_oid><key>psInputLineCVoltage</key><value_type>FLOAT</value_type><units>V</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>psSystemTotalACEnergy</name><type>SNMP_AGENT</type><snmp_oid>1.3.6.1.4.1.6302.2.1.2.11.11.0</snmp_oid><key>psSystemTotalACEnergy</key><value_type>FLOAT</value_type><units>kWh</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>psSystemTotalDCEnergy</name><type>SNMP_AGENT</type><snmp_oid>1.3.6.1.4.1.6302.2.1.2.11.12.0</snmp_oid><key>psSystemTotalDCEnergy</key><value_type>FLOAT</value_type><units>kWh</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>Total Load Current</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.12.1.0</snmp_oid><key>psTotalLoadCurrent</key><value_type>FLOAT</value_type><units>A</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item><item><name>Capacidade Usada dos Retificadores</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.3.0</snmp_oid><key>rectifiersUsedCapacity</key><units>%</units><applications><application><name>Operational</name></application></applications></item></items><discovery_rules><discovery_rule><name>Alarms Description</name><type>SNMP_AGENT</type><snmp_oid>discover[{#DESCR},SNMPv2-SMI::enterprises.6302.2.1.4.1.5]</snmp_oid><key>ifAlarmDescription</key><lifetime>0</lifetime><item_prototypes><item_prototype><name>{#DESCR}</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.4.1.4.{#SNMPINDEX}</snmp_oid><key>if[{#DESCR}]</key><applications><application><name>Operational</name></application></applications><valuemap><name>AlarmVertiv</name></valuemap><preprocessing><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>1m</params></step></preprocessing><trigger_prototypes><trigger_prototype><expression>{last()}=6</expression><name>{#DESCR} - CRITICAL</name><priority>HIGH</priority><manual_close>YES</manual_close></trigger_prototype><trigger_prototype><expression>{last()}=3</expression><name>{#DESCR} - WARNING</name><priority>AVERAGE</priority><manual_close>YES</manual_close></trigger_prototype></trigger_prototypes></item_prototype></item_prototypes></discovery_rule><discovery_rule><name>Battery</name><type>SNMP_AGENT</type><snmp_oid>discover[{#IFBATTERY},SNMPv2-SMI::enterprises.6302.2.1.2.5.5.1.3]</snmp_oid><key>ifBattery</key><lifetime>1h</lifetime><item_prototypes><item_prototype><name>{#IFBATTERY} - Capacidade</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.5.5.1.4.{#SNMPINDEX}</snmp_oid><key>ifBatteryRating[{#IFBATTERY}]</key><units>Ah</units><description>Tipo de Bateria Utilizada</description><applications><application><name>Inform</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step></preprocessing></item_prototype></item_prototypes></discovery_rule><discovery_rule><name>Retificadores</name><type>SNMP_AGENT</type><snmp_oid>discover[{#IFDESCR},SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.7]</snmp_oid><key>ifRetificadores</key><lifetime>1h</lifetime><item_prototypes><item_prototype><name>{#IFDESCR} - Capacidade da Corrente</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.6.{#SNMPINDEX}</snmp_oid><key>ifCurrentCapacity[{#IFDESCR}]</key><delay>1h</delay><value_type>FLOAT</value_type><units>A</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item_prototype><item_prototype><name>{#IFDESCR} - Falha no Retificador</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.8.{#SNMPINDEX}</snmp_oid><key>ifFailRectifyer[{#IFDESCR}]</key><delay>1h</delay><applications><application><name>Operational</name></application></applications><valuemap><name>PostgreSQL recovery role</name></valuemap><trigger_prototypes><trigger_prototype><expression>{last()}&lt;&gt;2</expression><name>Falha no Retificador</name><priority>HIGH</priority></trigger_prototype></trigger_prototypes></item_prototype><item_prototype><name>Hardware Version {#IFDESCR}</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.3.{#SNMPINDEX}</snmp_oid><key>ifHardwareVersion[{#IFDESCR}]</key><delay>1h</delay><trends>0</trends><value_type>CHAR</value_type><applications><application><name>Inform</name></application></applications></item_prototype><item_prototype><name>Product Model {#IFDESCR}</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.2.{#SNMPINDEX}</snmp_oid><key>ifProducModel[{#IFDESCR}]</key><delay>1h</delay><trends>0</trends><value_type>CHAR</value_type><applications><application><name>Inform</name></application></applications></item_prototype><item_prototype><name>Software Revision {#IFDESCR}</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.4.{#SNMPINDEX}</snmp_oid><key>ifSoftwareRevision[{#IFDESCR}]</key><delay>1h</delay><trends>0</trends><value_type>CHAR</value_type><applications><application><name>Inform</name></application></applications></item_prototype><item_prototype><name>{#IFDESCR} - Temperature</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.9.{#SNMPINDEX}</snmp_oid><key>ifTemperatura[{#IFDESCR}]</key><delay>1h</delay><value_type>FLOAT</value_type><units>℃</units><applications><application><name>Operational</name></application></applications><preprocessing><step><type>MULTIPLIER</type><params>0.001</params></step><step><type>DISCARD_UNCHANGED_HEARTBEAT</type><params>6h</params></step></preprocessing></item_prototype><item_prototype><name>Serial {#IFDESCR}</name><type>SNMP_AGENT</type><snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.5.{#SNMPINDEX}</snmp_oid><key>serial[{#IFDESCR}]</key><delay>1h</delay><trends>0</trends><value_type>CHAR</value_type><applications><application><name>Inform</name></application></applications></item_prototype></item_prototypes></discovery_rule></discovery_rules><macros><macro><macro>{$HOSTNAME}</macro><value>{#IFHOSTNAME}</value><description>HOSTNAME</description></macro></macros></template></templates><value_maps><value_map><name>AlarmVertiv</name><mappings><mapping><value>3</value><newvalue>Warning</newvalue></mapping><mapping><value>6</value><newvalue>Critical</newvalue></mapping></mappings></value_map><value_map><name>PostgreSQL recovery role</name><mappings><mapping><value>0</value><newvalue>Master</newvalue></mapping><mapping><value>1</value><newvalue>Standby</newvalue></mapping></mappings></value_map><value_map><name>PowerNet-MIB::upsBasicBatteryStatus</name><mappings><mapping><value>1</value><newvalue>Unknown</newvalue></mapping><mapping><value>2</value><newvalue>Normal</newvalue></mapping><mapping><value>3</value><newvalue>Low</newvalue></mapping><mapping><value>4</value><newvalue>In Fault Condition</newvalue></mapping></mappings></value_map></value_maps></zabbix_export>